Case: T09FR03570

Parcel: 13010001A


Addresses:

3102 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR03570

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2009 INSP - FULL Approved Approved
11/16/2009 INSP - FULL Correction Required FIRE INSPECTION REPORT

11-16-09
Shell
3102 East 22nd
Tucson, AZ


Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 11-16-2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about December 1st 2009.


703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.

" Replace the ceiling tiles to prevent the travel of smoke and flame in case of a fire.

1011.4 Internally illuminated exit signs. Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer's instructions and Section 2702 of the International Building Code. Exit signs shall be illuminated at all times.

" The exit signs in on the rear exit are not working. Please repair or replace the sign to ensure it is lit at all times and has a minimum of a 90 minute back up power source


605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

" Replace the missing outlet cover near the coke machine.

2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

" Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.

Section 3404.2.12.3 Existing tanks and piping. Existing underground storage tanks and piping shall be tested for leakage at the owner's or operator's expense at least every 24 months in accordance with this section.

EXCEPTION: Underground storage tank systems with an approved method of detecting leaks from any component of the system.

Tanks shall be emptied of flammable or combustible liquids if required tests are not completed within the specified time.
When testing is required, owners or operators shall provide the fire code official with data setting forth the method of testing that is to be used and shall submit the name of a qualified individual who will conduct the test.

A testing permit shall be obtained. The method of testing to be used shall consider the effects of temperature, pressure and other variables and shall establish conclusively whether the tank or piping is leaking. Pneumatic testing is prohibited.

Devices used for final testing shall be capable of detecting leaks as small as 0.05 gallon per hour. Leaking piping and equipment shall not be used until repaired or replaced. The fire code official is authorized to require that the test be conducted in the code official's presence.

" Please provide a copy of either the tank tightness and line leak test results or if a automatic tank gauge system is used please provide the annual calibration test report for that device and the print out showing that the system has passed its leak test.


2205.2.2 Emergency shutoff valves. Automatic emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

Spill control. Maintain enough "drysorb" material and a container to handle small spills.

" Kitty litter, broom, dust pan and 5 gallon pail will suffice.



Re-Inspected by __________________ Approved Disapproved


Sincerely,



Conrad Funke
Fire Inspector
Tucson Fire Department
797 E. Ajo
Tucson, AZ 85713-5011
(520) 791-4502 Ext. 102