Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR03518

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAV EBBEN CORRECTED. F/A AND SPRINKLER SYSTEM ANNUAL INSP. REPORTS SUBMITTED. 5 YEAR CHECK VALVE INSP. DONE 2009.
11/13/2009 INSP - FULL Violation 12.) TFC 605.6 OPEN WIRE SPLICE IN CLOSET OF COUNTRY STORE MUST BE ENCOLSED IN AN APPROVED JUNCTION BOX.
11/13/2009 INSP - FULL Violation 13.) TFC 1006.3 SERVICE/REPAIR EMERGENCY ILLUMINATION UNIT IN HALLWAY BY ROOM #118.
11/13/2009 INSP - FULL Violation 14.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN HALLWAY BY ROOM # 2225.
11/13/2009 INSP - FULL Violation 15.) TFC 1006.3 SERVICE/REPAIR EMERGENCY ILLUMINATION UNIT BE MAIN FLOOR ELEVATOR.
11/13/2009 INSP - FULL Violation 16.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN UTILITY ROOM BY ROOM #240.
11/13/2009 INSP - FULL Violation 17.) TFC 703.1.1 SEAL (4) CEILING PENETRATIONS IN 2ND FLOOR DINING ROOM.
11/13/2009 INSP - FULL Violation 18.) TFC 1006.3 SERVICE/REPAIR EMERGENCY ILLUMINATION UNIT IN 2ND FLOOR DINING ROOM.
11/13/2009 INSP - FULL Violation 19.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN 2ND FLOOR DINING ROOM.
11/13/2009 INSP - FULL Violation 20.) TFC 901.6 REPLACE (4) MISSING ESCUTCHEONS IN 2ND FLOOR NURSE'S OFFICE.
11/13/2009 INSP - FULL Violation 21.) TFC 1006.3 SERVICE/REPAIR EMERGENCY ILLUMINATION UNIT IN 2ND FLOOR HALLWAY BY STAFF ROOM.
11/13/2009 INSP - FULL Violation 22.) TFC 605.5 THE EXTENSION CORD IN 2ND FLOOR CARE GIVERS ROOM CANNOT BE A SUBSTITUTE FOR PERMANENT WIRNING.
11/13/2009 INSP - FULL Violation 23.) TFC 1006.3 SERVICE/REPAIR EMERGENCY ILLUMINATION UNIT BY ROOM # 202.
11/13/2009 INSP - FULL Violation 24.) TFC 901.6.2 FIRE ALARM AND SPRINKLER SYSTEM ANNUAL INSPECTION REPORTS MUST BE SUBMITTED UPON RE-INSPECTION.
11/12/2009 INSP - FULL Violation 1.) TFC 1006.3 SERVICE/PERAIR EMERGENCY ILLUMINATION UNIT ON NORTH WALL OF KITCHEN.
11/12/2009 INSP - FULL Violation 2.) TFC 901.6 INSULATE AROUND SPRINKLER HEAD IN KITCHEN FREEZER UNIT.
11/12/2009 INSP - FULL Violation 3.) TFC 703.1.1 SEAL CEILING PENETRATION IN BASEMENT ABOVE WATER HEATERS.
11/12/2009 INSP - FULL Violation 4.) TFC 703.1.1 SEAL CEILING PENETRATION IN BASEMENT HOUSE KEEPING ROOM.
11/12/2009 INSP - FULL Violation 5.) TFC 906.2 HAVE EXTINGUISHER IN LAUNDRY INSPECTED.
11/12/2009 INSP - FULL Violation 6.) TFC 605.4 CUBE TYPE MULTI-PLUG ADAPTER IN BEAUTY SALON IS NOT PERMITTED.
11/12/2009 INSP - FULL Violation 7.) TFC 605.4 CUBE TYPE MULTI-PLUG ADAPTER IN LIBRARY IS NOT PERMITTED.
11/12/2009 INSP - FULL Violation 8.) TFC 901.6 PUSH ESCUTCHEON INTO PLACE IN BOTTOM FLOOR HALLWAY BY ELEVATOR.
11/12/2009 INSP - FULL Violation 9.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN BOTTOM HALLWAY BY ELEVATOR.
11/12/2009 INSP - FULL Violation 10.) 901.6 REPLACE MISSING ESCUTCHEON IN HALLWAY BY ROOM # 2101.
11/12/2009 INSP - FULL Violation 11.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN MAIN FLOOR UTILITY ROOM BY ROOM # 122.