Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/01/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 11/12/2009 |
INSP - FULL |
|
Violation |
1.) TFC 1008.1.8 SERVICE STICKING EXIT DOOR FROM SCHOOL AGE ROOM. |
| 11/12/2009 |
INSP - FULL |
|
Violation |
2.) TFC 901.6 SEAL AROUND SPRINKLER HEAD IN BATHROOM BETWEEN EARLY LEARNERS AND EXPLORATION STATION ROOMS. |
| 11/12/2009 |
INSP - FULL |
|
Violation |
3.) TFC 1008.1.8 THE SLIDE BOLT LATCHES ON BOTH KITCHEN DOORS MUST BE REMOVED. |
| 11/12/2009 |
INSP - FULL |
|
Violation |
4.) TFC 1008.1.8 SERVICE STICKING NORTH EXIT DOOR FROM KITCHEN. |
| 11/12/2009 |
INSP - FULL |
|
Violation |
5.) TFC 316.2 CLEAN LINT AND COMBUSTIBLES FROM BEHIND CLOTHES DRYER IN LAUNDRY ROOM. |
| 11/12/2009 |
INSP - FULL |
|
Violation |
6.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN COPIER ROOM. |
| 11/12/2009 |
INSP - FULL |
|
Violation |
7.) TFC 901.6 THE SPRINKLER SYSTEM MAIN SHUT OFF MUST BE CHAINED AND LOCKED IN OPEN POSITION. |
| 11/12/2009 |
INSP - FULL |
|
Violation |
8.) TFC 901.6.2 THE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM ANNUAL INSPECTION REPORTS MUST BE SUBMITTED UPON RE-INSPECTION. |