Case: T09FR03455

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR03455

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/04/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

_____1. Remove all storage from obstructing the working space of the electrical panels.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)


Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____