Case: T09FR03443

Parcel: 13602715A


Addresses:

8150 E 22ND ST #160


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR03443

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2009 INSP - FULL Approved
11/02/2009 INSP - FULL Correction Required D & D Automatic
ATTN: Don Calhoon
8150 E. 22nd St. #160
Tucson, AZ. 85710

Dear Mr. Calhoon

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on November 2, 2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). A Re-inspection will be performed on or about
November 16, 2009

Notice of Violations:
1.______1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

- Require Action: Remove appliances that are blocking the exit

2._____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances:

- Required Correction:
i. Remove extension cords on the North wall of the service area (2 each)
ii. Remove extension cord near the bathroom

3._____ 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied
- Required Action: Mount fire extinguishers

4._____ 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited

- Required Action: Remove unapproved multiplug adapter (North wall)

The Tucson Fire Department is committed to the protection of your property. Your help as a business owner and as a citizen is greatly appreciated.