Case: T09FR03372

Parcel: 11105006B


Addresses:

3155 N ALVERNON WY

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/27/2009 INSP - FULL Approved Approved
07/27/2009 INSP - FULL Correction Required FIRE INSPECTION REPORT

07-27-2009
3155 N. Alvernon.
Tucson, AZ
Circle K # 517

Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 07-27-2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about August 10th 2009.


906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.

906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

" Mount the extinguishers in accordance with the above standards in a visible location.


901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

" Fire extinguishers shall be inspected annually; both extinguishers were last serviced in 2007.