Case: T09FR03367

Parcel: 13106029B

Inspection Status: Prior to Intermediates

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/23/2009 INSP - FULL Prior to Intermediates Rear door SHALL NOT be used as an EXIT through the machine shop. Panic Hardware shall be removed prior to occupancy.

TFC 1014.2 - Egress through intervening spaces.
Egress through intervening spaces shall comply with this section.
1. Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not a high-hazard occupancy and provide a discernible path of egress travel to an exit.
Exception: Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H, S or F occupancy when the adjoining or intervening rooms or spaces are the same or a lesser
hazard occupancy group.
TFC 1014.2.1 - Multiple tenants.
Where more than one tenant occupies any one floor of a building or structure, each tenant space, dwelling unit and sleeping unit shall be provided with access to the required exits without passing through adjacent tenant spaces.