Case: T09FR03350

Parcel: 12402008A


Addresses:

1801 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
02/01/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
10/23/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Fire alarm needs annual inspection.
____Sprinkler system due for annual inspection.
____Test every smoke detector in bedrooms. Provide smoke detector testing log upon reinspection.
10/23/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.4 Extinguishing system service. Automatic
fire-extinguishing systems shall be serviced at least
every 6 months and after activation of the system.
Inspection shall be by qualified individuals, and a certificate
of inspection shall be forwarded to the fire code official
upon completion.

____Commercial cooking extinguishing system due for 6 month inspection. Provide report. Repair any deficiencies.
10/23/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____Fire extinguishers due for annual inspection. Service and tag.