Case: T09FR03279

Parcel: 12112416C


Addresses:

5426 E PIMA ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
11/02/2009 INSP - FULL Approved ALL NOTED TFC VILATIONS HAVE BEEN CORRECTED. SPRINKLER SYSTEM ANNUAL INSP. REPORT WAS SUBMITTED. 5 YEAR CHECK VALVE INSP DONE IN 2007. APPROVED.
10/16/2009 INSP - FULL Violation 1.) TFC 605.6 A COVER PLATE IS REQUIRED ON ELECTRICAL JUNCTION BOX ON CEILING BY EAST WALL IN THE MIDDLE OF THE BUILDING.
10/16/2009 INSP - FULL Violation 2.) TFC 605.6 A COVER PLATE IS REQUIRED ON ELECTRICAL JUNCTION BOX ON CEILING BY EAST WALL ABOVE THE DRESSING ROOMS.
10/16/2009 INSP - FULL Violation 3.) TFC 901.6 REMOVE PLASTIC FROM SPRINKLER HEAD EAST SIDE SOUTH OF DRESSING ROOMS.
10/16/2009 INSP - FULL Violation 4.) TFC 901.6 REMOVE OVER HEAD STORAGE IN BACK STORAGE ROOM BLOCKING SPRINKLER COVERAGE.
10/16/2009 INSP - FULL Violation 5.) TFC 605.6 TWO ELECTRICAL JUNCTION BOXES ON CEILING AT WEST WALL BY REAR COUNTER NEED COVER PLATES.
10/16/2009 INSP - FULL Violation 6.) TFC 901.6.2 THE SPRINKLER SYSTEM ANNUAL INSPECTION REPORT MUST BE SUBMITTED AT TIME OF RE-INSPECTION.