Case: T09FR03146

Parcel: 113052570

Inspection Status: Approved

Inspection History: INSP - SELF INSPECTION PROGRAM

Case Number - T09FR03146

Inspection Description - INSP - SELF INSPECTION PROGRAM

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2009 INSP - SELF INSPECTION PROGRAM Approved Panels are labeled, and clearance is provided. Building is being renovated/altered.
10/02/2009 INSP - SELF INSPECTION PROGRAM Violation 1.IFC 605.3: Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated.
10/02/2009 INSP - SELF INSPECTION PROGRAM Scheduled RI - 10/15/09