Case: T09FR03015

Parcel: 121060070


Addresses:

5667 E SPEEDWAY BL


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR03015

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
09/15/2009 VIOL - BUILDING SVCS & SYSTEMS Violation IFC.605.3 Working space and clearance.
A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

____Electrical panel in rear of building requires access clearance.
09/15/2009 VIOL - BUILDING SVCS & SYSTEMS Violation IFC.605.6 Unapproved conditions.
Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

____Main office and front of building West side need electrical cover plates.

IFC.605.4.2 Power supply.
Relocatable power taps shall be directly connected to a permanently installed receptacle.

____Two electrical power taps must be pluged directly into wall outlet in office 2.