Inspection Status: Approved
Inspection History: INSP - AST
Case Number - T09FR02773
Inspection Description - INSP - AST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2009 | INSP - AST | Approved | Permit issued for 1x 400 gallon used oil. 3 x 330 gallon new oil tanks | |
08/27/2009 | INSP - AST | Correction Required | FIRE INSPECTION REPORT 08-27-09 Brake Masters 7855 East Speedway Tucson, AZ 85710 Dear Sir or Madam, The Tucson Fire Department has conducted a fire safety inspection at the above stated business on August 27, 2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about September 10th 2009. 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. - Emergency venting shall be installed on the red 275 gallon tank. 3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent. - Install normally closed vents on all 4 tanks. Re-Inspected by __________________ Approved Disapproved Sincerely, Conrad Funke Fire Inspector Tucson Fire Department 797 E. Ajo Tucson, AZ 85713-5011 (520) 791-4502 Ext. 102 |