Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/22/2009 INSP - FULL Correction Required 07-22-2009
130 East Speedway.
Tucson, AZ
Circle K #166

Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 07-22-2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about August 5th 2009.


1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

" Keep the exit path in rear of the store clear of obstructions.



605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

" Replace or repair the outlet located near the water dispenser outside.


906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.

906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

" Mount the extinguishers in accordance with the above standards in a visible location.


901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

" Fire extinguishers shall be inspected annually; both extinguishers were last serviced in 2007.



Property Representative _____________________


Re-Inspected by __________________ Approved Disapproved