Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2009 | VIOL - MEANS OF EGRESS | Violation | IFC.1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. ___Two (2) Exit Signs in Blg 203 must be serviced repaired. |