Case: T09FR02709

Parcel: 13217141B


Addresses:

1101 E PALMDALE ST

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/19/2009 INSP - FULL Violation 1011.3 Tactile exit signs. A tactile sign stating EXIT and complying
with ICC A117.1 shall be provided adjacent to each
door to an egress stairway, an exit passageway and the exit discharge.
1011.4 Internally illuminated exit signs. Internally illuminated
exit signs shall be listed and labeled and shall be installed
in accordance with the manufacturer’s instructions and Section
2702 of the International Building Code. Exit signs shall be
illuminated at all times.
Illuminate all exit signs.
08/19/2009 INSP - FULL Violation 1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply.In the event of power supply failure, an emergency electrical
system shall automatically illuminate the following areas:
1. Aisles and unenclosed egress stairways in rooms and
spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in buildings
required to have two or more exits.
3. Exterior egress components at other than the level of exit
discharge until exit discharge is accomplished for buildings
required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section
1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for
exit discharge doorways in buildings required to have
two or more exits.
The emergency power system shall provide power for a
duration of not less than 90 minutes and shall consist of storage
batteries, unit equipment or an on-site generator. The installation
of the emergency power system shall be in accordance
with Section 2702 of the International Building Code.