Case: T09FR02698

Parcel: 133291810


Addresses:

8467 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/12/2009 VIOL - BUILDING SVCS & SYSTEMS Approved
09/04/2009 VIOL - BUILDING SVCS & SYSTEMS Partial Approval All done except decal on elect room
08/18/2009 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical wires extending through walls:
TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors.
______ Please remove wires.
08/18/2009 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:
TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
_____ Remove or replace with approved fused power strip.
08/18/2009 VIOL - BUILDING SVCS & SYSTEMS Violation Open space in electrical panel / locks on breakers / crushed cord:
TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.
_____Place an approved "blank" in the space.
_____ Remove locks from breakers, or show proof of electrician approval.
______ Remove cord from under bookshelf
08/18/2009 VIOL - BUILDING SVCS & SYSTEMS Violation Elecreical room ident:
605.3.1 Labeling. Doors into electrical control panel rooms
shall be marked with a plainly visible and legible sign stating
ELECTRICAL ROOM or similar approved wording.
The disconnecting means for each service, feeder or branch
circuit originating on a switchboard or panelboard shall be
legibly and durably marked to indicate its purpose unless
such purpose is clearly evident.

_____Place a Red 2" or 3" letters on White background decal for the above effect.