Case: T09FR02681

Parcel: 13329012G


Addresses:

8545 E BROADWAY BL

Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Date Description Inspector Results Comments
10/21/2009 VIOL - MOTOR FUEL DISPENSING Approved Fuel shut off works great! All approved
08/17/2009 VIOL - MOTOR FUEL DISPENSING Violation Fuel emergency shut off:
IFC 2006: 2203.2 Emergency disconnect switches. An approved,
clearly identified and readily accessible emergency disconnect
switch shall be provided at an approved location, to stop the
transfer of fuel to the fuel dispensers in the event of a fuel spill
or other emergency. An emergency disconnect switch for
exterior fuel dispensers shall be located within 100 feet (30 480
mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers.
For interior fuel-dispensing operations, the emergency
disconnect switch shall be installed at an approved
location. Such devices shall be distinctly labeled as: EMERGENCY
FUEL SHUTOFF. Signs shall be provided in approved locations.
_______ install an approved switch.