Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2009 | VIOL - MEANS OF EGRESS | Approved | ||
| 08/14/2009 | VIOL - MEANS OF EGRESS | Violation | Exit access, exit, and discharge path blocked: 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. ______ Clear exit path and keep it clear [36" minimum] -Bush outside South exit door of Fitness building. |
|
| 08/14/2009 | VIOL - MEANS OF EGRESS | Violation | Bolt lock: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. [upstairs exit from wedding facility] ______Remove bolt lock. |
|
| 08/14/2009 | VIOL - MEANS OF EGRESS | Violation | Double keyed lock on door: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove Keyed dead bolt. Front door -wedding facility. |
|
| 08/14/2009 | VIOL - MEANS OF EGRESS | Violation | Exit signs not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light and back up battery in exit signs. |
|
| 08/14/2009 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |