Case: T09FR02678

Parcel: 13303303C


Addresses:

1501 N HOUGHTON RD

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
10/12/2009 VIOL - FIRE PROTECTION SYSTEMS Approved
08/14/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not mounted:
TFC2006/ 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

______ Mount extinguishers in an approved manner.
08/14/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not tagged / inspected:
TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code.
08/14/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishing system service: Kitchen hood-
904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

______ Hood system to be serviced, tested and tagged every 6 months. Have ALL deficiencies fixed, and deliver a copy of report to Inspector Cobb.
08/14/2009 VIOL - FIRE PROTECTION SYSTEMS Violation Sprinkler system:
903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901.



_______ System to be tested, and tagged annually.