Case: T09FR02678

Parcel: 13303303C


Addresses:

1501 N HOUGHTON RD

Inspection Status: Approved

Inspection History: VIOL - INT.FINISH, DEC. MATL'S

Date Description Inspector Results Comments
10/12/2009 VIOL - INT.FINISH, DEC. MATL'S Approved Treated material with retardent. Ma 30 unable to burn material. Approved. Instructed manager to periodically test for flame retardant life using a test sample treated at the same time. Manager agreed.
08/14/2009 VIOL - INT.FINISH, DEC. MATL'S Violation Ceiling / wall - decorations:
TFC 805.1 General. In occupancies of Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings
shall be flame resistant in accordance with Section 805.2 and NFPA 701 or be noncombustible.

_____ Remove ceiling and wall decorations [material / cloth] from the Yoga rm and the wall of the dance room. Proof of fire proofing and approval by the Fire Marshal must be granted before replacing.
[Approved - see below]
Re-inspection date scheduled on or after August 28th, 2009.
If you have any questions or concerns please call Inspector Cobb at 791-4502
Thank you,

_____________________________________________
Brian Cobb, Inspector, Tucson Fire Department


__________________________ - I have received a copy of this inspection report.
Building Representative


Re-inspection approved: ___________________________Date:__________