Case: T09FR02620

Parcel: 11306057A


Addresses:

3375 N CAMPBELL AV

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
08/06/2009 VIOL - MEANS OF EGRESS Violation IFC.1006.1 Illumination required.
The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.

____None of the egress lights operated when the test button was pushed.

IFC.1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

____Dead bolt shall be removed from door on North exit which has panic hardware.