Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | IFC.901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Inspection and testing of sprinkler system shall be in compliance with NFPA 25. ____The five (5) year check valve test is required. ____Spare sprinkler heads are required in sprinkler head box. |