Case: T09FR02620

Parcel: 11306057A


Addresses:

3375 N CAMPBELL AV

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
08/06/2009 VIOL - BUILDING SVCS & SYSTEMS Violation IFC.605.3 Working space and clearance.
A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

____Maintain 30 inch clearance around electrical service panel in two rooms, phone room being one of the rooms.
08/06/2009 VIOL - BUILDING SVCS & SYSTEMS Violation IFC.605.5 Extension cords.
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

____Extension cord shall not be used as permanent in Ted Ranney office.