Case: T09FR02611

Parcel: 11522002A


Addresses:

1390 W SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/05/2009 INSP - FULL Approved Annual MAITS Inspection of the El Rio Neighborhood Center had the following violations: Day Care Sec. # 605 repair/replace male cord cap on vaccuum cleaner. Corrected by F&M 5-Jun. Sec. #605.4.1 Repair/replace damaged GFCI's to the following areas.South outside wall Bldg. #D-2. Pottery Room, East wall. Salt River Room, Kitchen South wall. Corrected by F&M 23-Jun. Sec.# 906.6 Provide Fire Extinguisher signs in the following locations: door # 1B and door # D2. Signs up by 25-Jun. Sec. # 1004.3 Auditorium Occupancy Load Signs shall be posted. Signs posted in each room by 12-Jun. Sec. # 1006.1 Bldg. #D2 Install Exit lighting over door #3. Corrected by F&M 14-Jul. Bldg. C-1 Sec. #1006.1 repair/replace malfunctioning emergency lights in Dance area East wall. Corrected by F&M 14-Jul. Sec. #315.2.3 Combustible material shall be removed from Mechanical Room behind door # A-23. Room cleared out by 21-Jul