Case: T09FR02553

Parcel: 125011200


Addresses:

3033 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR02553

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
07/31/2009 VIOL - BUILDING SVCS & SYSTEMS Violation IFC.605.3 Working space and clearance.
A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

____ Remove boxes from around electrical service panel in the upstairs telephone room.

____Remove boxes from around electrical service panel in the telephone room down stairs.
07/31/2009 VIOL - BUILDING SVCS & SYSTEMS Violation IFC.605.5 Extension cords.
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances

____Extension cords shall not be used as permanent wiring in the down stairs vault room.

IFC.605.6 Unapproved conditions.
Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

____ Open junction box in computer room requires cover plate in the computer room down stairs.