Case: T09FR02538

Parcel: 12404102A


Addresses:

901 E UNIVERSITY BL

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/30/2009 INSP - FULL Correction Required DURING THE ANNUAL INSPECTION THE FOLLOWING DEFICIENCY WAS FOOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR WORK SHALL BE FORWARDED TO THIS OFFICE

1) WATER FLOW DID NOT ANNUNCIATE AT THE ALARM PANEL AND SHALL BE IN REPAIR

2) SUPERVISORY NOTIFICATION DID NOT ANNUNCIATE AT THE ALARM PANEL

3) IF GUAGES ARE 5 YEARS OLD THEY SHALL BE CHANGED OUT OR CALIBRATED.

4) THE INTERNAL VALVE IS DUE FOR THE 5 YEAR INSPECTION