Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR02538
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL INSPECTION THE FOLLOWING DEFICIENCY WAS FOOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR WORK SHALL BE FORWARDED TO THIS OFFICE 1) WATER FLOW DID NOT ANNUNCIATE AT THE ALARM PANEL AND SHALL BE IN REPAIR 2) SUPERVISORY NOTIFICATION DID NOT ANNUNCIATE AT THE ALARM PANEL 3) IF GUAGES ARE 5 YEARS OLD THEY SHALL BE CHANGED OUT OR CALIBRATED. 4) THE INTERNAL VALVE IS DUE FOR THE 5 YEAR INSPECTION |