Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T09FR02524
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____ The hood system in your building has been found unfit and requires a cleaning. You are to have your hood system cleaned immediately and provide the proper paper work to prove that the required cleaning has been done professionally. |