Case: T09FR02485

Parcel: 120082500


Addresses:

4764 S 6TH AV

Inspection Status: Violation

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
07/28/2009 VIOL - PRECAUTION AGAINST FIRE Violation 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction.
__Remove propane tank used for cooking from building.
07/28/2009 VIOL - PRECAUTION AGAINST FIRE Violation 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
___ Reduce amount of pinatas stored inside bulding.
07/28/2009 VIOL - PRECAUTION AGAINST FIRE Violation 315.2.2 - Means of egress. Combustible materials shall not be stored in exits or exit enclosures.