Case: T09FR02439

Parcel: 133110150


Addresses:

7401 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T09FR02439

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Approved

Date Description Inspector Results Comments
09/04/2009 VIOL - PRECAUTION AGAINST FIRE Approved All approved - good job! closed
07/24/2009 VIOL - PRECAUTION AGAINST FIRE Violation BBQ's on balcony and below ramada:
TFC 308.3.1 Open-flame cooking devices. Charcoal burners and other open-flame cooking devices shall not be operated on combustible balconies or within 10 feet (3048 mm) of combustible construction.

308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction.

______ Remove all BBQ's from balcony areas. [and keep it this way]

______ Move BBQ from below ramada [approx 5 feet from structure]


Re-inspection date scheduled on or after August 7th, 2009.
If you have any questions or concerns please call Inspector Cobb at 791-4502
Thank you,

_____________________________________________
Brian Cobb, Inspector, Tucson Fire Department


__________________________ - I have received a copy of this inspection report.
Building Representative


Re-inspection approved: ___________________________