Case: T09FR02436

Parcel: 132166160


Addresses:

845 E OHIO ST


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T09FR02436

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
07/23/2009 INSP - FULL Violation 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.
Exception: Approved self-luminous signs that provide
evenly illuminated letters shall have a minimum luminance
of 0.06 foot-lamberts (0.21 cd/m2).
1027.4 Power source. Where emergency illumination is
required in Section 1027.5, exit signs shall be visible under
emergency illumination conditions.
Exception: Approved signs that provide continuous illumination
independent of external power sources are not
required to be connected to an emergency electrical system.
1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress:
Maintain isle paths throughout the warehouse.
07/23/2009 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.
07/23/2009 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
Do not block panels.
07/23/2009 INSP - FULL Violation 1003.6 Means of egress continuity. The path of egress travel
along a means of egress shall not be interrupted by any building
element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the requiredwidth of a means of egress except projections permitted by this
chapter. The required capacity of a means of egress system
shall not be diminished along the path of egress travel.
Maintain isle paths throughout.