Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T09FR02428

Parcel: 12710178C

Inspection Status: Correction Required

Inspection History: INSP - SELF INSPECTION PROGRAM

Case Number - T09FR02428

Inspection Description - INSP - SELF INSPECTION PROGRAM

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/23/2009 INSP - SELF INSPECTION PROGRAM Correction Required " 1IFC 901.6: If you have a fire extinguisher in your building, has it been serviced within the past 12 months?
Fire extinguishers shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
07/23/2009 INSP - SELF INSPECTION PROGRAM Correction Required " 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
07/23/2009 INSP - SELF INSPECTION PROGRAM Correction Required 2. IFC 315.2.1: Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
07/23/2009 INSP - SELF INSPECTION PROGRAM Correction Required 3. IFC 305.1 Clearance from ignition sources. Clearance between ignition sources, such as luminaires, heaters, flame-producing devices and combustible materials, shall be maintained in an approved manner.