Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2009 | VIOL - FIRE PROTECTION SYSTEMS | Approved | All deficiencies corrected. INSPECTOR:________________ CAPTAIN:_________________ |
|
| 08/18/2009 | VIOL - FIRE PROTECTION SYSTEMS | Continued | Met with the property rep and Greg, A-AAA sprinkler co. to discuss the sprinkler system inspection results. All items must be corrected: escept the need to sprinkler the booth where they apply the polyester powder coating. The powder is not flammable nor explosive. Sprinkler protection is not required for this application. A final inspection will be conducted once the sprinkler deficiencies are corrected. | |
| 07/21/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. The FIre SPrinkler System is overdue its annual servicing / inspection. Have system serviced. INTERNATIONAL FIRE CODE (IFC) 901.6.1 Standards. Fire protection systems shall be inspected, tested annaully and maintained in accordance with the referenced standards. |