Case: T09FR02396

Parcel: 13323087J


Addresses:

7499 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR02396

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
09/04/2009 VIOL - MEANS OF EGRESS Approved
08/11/2009 VIOL - MEANS OF EGRESS Partial Approval Exits are clear / bolt lock removed.
07/20/2009 VIOL - MEANS OF EGRESS Violation Blocked exit:
1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_______Clear exit area, and maintain it this way. [x2]
07/20/2009 VIOL - MEANS OF EGRESS Violation Bolt lock:
TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

______Remove bolt lock. [on main leaf of back door]
07/20/2009 VIOL - MEANS OF EGRESS Violation Emergency lighting:
IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.
07/20/2009 VIOL - MEANS OF EGRESS Violation Exit sign not lit:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.

_____Fix light in exit sign.