Case: T09FR02334

Parcel: 13608477J

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR02334

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2009 INSP - FULL Approved Complete
07/16/2009 INSP - FULL Correction Required 07-16-2009
9515 E Golf Links
Tucson, AZ
Circle K #8744

Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 07-16-2009. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about July 30th 2009.


703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.

" Repair holes in ceiling and replace all missing ceiling tiles to prevent the travel of smoke and flame in case of a fire.


605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

" Replace the broken outlet cover in the back hallway.


906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.

906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

" Mount the extinguishers in accordance with the above standards