Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2009 | INSP - FULL | Violation | 1). currently all closures on laundry chutes are not closing. All these shall close. IFC 703.2.2 2). All combustible material shall be at least 30 inches from electrical equipment. Currently 8,th, 6th , 4th floor electrical rooms. IFC 605.3 3). Chairs are within 18 inches of sprinkler head in 3rd floor. Housekeeping room. IFC 315.2.1 4). Breakfast kitchen: Controls to hood system is blocked refrigerators and pans. These shall be moved. IFC 901.6 5). Fire drill required. Date of drill shall be determined by 8-3-09. 6). Annual automatic fire sprinkler report due. all required deficiencies shall be required. IFC 901.6 7). Annual fire pump test due. IFC 901.6 8). Annul Fire alarm test report due. IFC901.6 |