Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2009 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
1.) TFC 605.5 THE EXTENSION CORD IN INPATIENT ADVOCATE OFFICE POWERING THE POWER STRIP IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
2.) TFC 315.2.3 REMOVE THE COMBUSTIBLE STORAGE IN ELECTRICAL EQUIPMENT ROOM ACROSS FROM ELIZABETH THOMAS' OFFICE. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
3.) TFC 703.1.1 SEAL AROUND ELECTRICAL CONDUIT IN ELECTRICAL EQUIPMENT ROOM. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
4.) TFC 901.6 REPACE MISSING SPRINKLER HEAD ESCUTCHEON IN MEDICAL RECORDS SUPERVISOR'S OFFICE. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
5.) TFC 605.4.2 POWER STRIPS CANNOT BE PIGGY BACKED IN SUITE CLERKS WORK STATION BETWEEN SAI'S AND MARY'S WORK STATIONS. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
6.) TFC 605.4.2 POWER STRIPS CANNOT BE PIGGY BACKED IN SUITE CLERKS AREA BY THE COPY MACHINE. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
7.) TFC 605.4.2 POWER STRIPS CANNOT BE PIGGY BACKED IN PHYSICAL THERAPY SUPERVISOR'S OFFICE. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
8.) TFC 703.1.1 REPAIR CEILING PENETRATION IN APPOINTMENT SCHEDULING ROOM OF SUITE 260. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
9.)TFC 703.1.1 PUT CEILING TILE BACK IN PLACE IN APPOINTNMENT SCHEDULING ROOM OF SUITE 260. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
10.) TFC 703.1.1 PUT CEILING TILE BACK IN PLACE IN RESEARCH LAB OF SUITE 260. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
11.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN PHYSICIANS REST ROOM OF SUITE 260. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
12.) TFC 703.1.1 REPAIR CEILING PENETRATION IN EMPLOYEE'S LOUNGE OF SUITE 260. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
13.) TFC 703.1.1 REPAIR WALL PENETRATIONS IN EMPLOYEE'S LOUNGE OF SUITE 260. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
14.) TFC 703.1.1 SEAL CEILING PENETRATION IN METAL PLATE ABOVE VIDEO PROJECTOR IN EMPLOYEE'S LOUNGE OF SUITE 260. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
15.) TFC 605.4.2 PIGGY BACKING POWER STRIPS IN CUBICLE FOR MEDICAL RECORDS OF 2ND FLOOR IS NOT PERMITTED. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
16.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN CHART REVIEW OFFICE. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
17.) TFC 315.2.1 MAINTAIN SHELF STORAGE 18" BELOW SPRINKLER HEAD DELECTOR IN RTHO SUPPLY ROOM. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
18.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN HALLWAY OUTSIDE OF ORTHO SUPPLY ROOM OF SUITE 230. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
19.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN HALLWAY OUTSIDE OF DRESS ROOM # 2 OF SUITE 230. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
20.) TFC 901.6 REPLACE MISSING ESCUTCHEON IN EQUIPMENT ROOM IN BACK HALLWAY OF SUITE 230. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
21.) TFC 605.5 IN DR. BRAINARD'S OFFICE, SUITE 230, THE EXTENSION CORD CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
22.) TFC 703.1.1 REPAIR CEILING PENETRATION AND FIRE SEAL AROUND CABLES IN JANITOR'S CLOSET OF SUITE 230. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
23.)TFC 901.6 REPLACE MISSING ESCUTCHEON NEAR CHECK OUT AREA OF SUITE 200. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
24.) TFC 901.6 REPACE MISSING ESCUTCHEON IN HALLWAY BY EXAM ROOM 3 OF SUITE 200. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
25.) TFC 605.5 THE EXTENSION CORD IN DR. EVANS' OFFICE OF SUITE 200 CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 07/09/2009 |
INSP - FULL |
|
Violation |
26. TFC 703.1.1 SEAL AROUND PIPE IN E/S CLOSET OF SUITE 200. |