Inspection Status: Correction Required
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS AND A COPY OF THE REPAIR INVOICE SENT TO THIS OFFICE 1) THERE IS A PROBLEM WITH THE CHECK VALVE. ACCORDING TO OUR RECORDS IT IS DUE FOR THE FIVE YEAR INTERNAL INSPECTION. THIS MAY CORRECT THE PROBLEM 2) THERE IS CORROSION AND CALCIUM BUILDUP ON PIPING ABOVE THE CHECK VALVE WHICH COULD HAVE BEEN CAUSED BY A LEAK. TO PREVENT FURTHER PROBLEMS, POSSIBLE BLOWOUT, THE PIPE SECTION NEEDS TO BE CHANGED OUT. |