Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T09FR02237
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/12/2009 | VIOL - MEANS OF EGRESS | Approved | ||
07/08/2009 | VIOL - MEANS OF EGRESS | Violation | Blocked exit: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _______Clear exit area, and maintain it this way. |
|
07/08/2009 | VIOL - MEANS OF EGRESS | Violation | Exit signs: TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. ______Place exit signs in an approved manner over the doors in the news room. |
|
07/08/2009 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. ______ Fix permanant stairwell lighting in the lower area too. |