Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS AND A COPY OF THE REPAIR ORDER IS TO BE SENT TO THIS OFFICE 1) REPLACE THE 5 SPRINKLER HEADS, OUTSIDE WEST AREA, THAT ARE PAINTED 2) THE WATER MOTOR GONG IS INOPERATIVE, IT AHALL BE REPAIRED OR REPLACED 3) REPAIR THE PIPE HANGER AT THE WATER MOTOR GONG 4) STORAGE CLOSETS SHALL HAVE SPRINKLERS INSTALLED, IN THE ROOM WHERE INSPECTORS TEST IS LOCATED 5) THE SPRINKLER HEAD IN THE S/W LADIES ROOM SHALL NOT BE OBSTRUCTED, RELOCATE IF NECESSARY 5) THE SYSTEM SIDE GUAGE IS DUE FOR REPLACEMENT. RECOMMENDED TO CHANGE BOTH GUAGES. |