Case: T09FR02193

Parcel: 13309109A


Addresses:

8151 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
11/10/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
07/06/2009 INSP - FULL Violation 1.) TFC 316.2 LINT TRAP FOR CLOTHES DRYER MUST BE CLEANED OFTEN AS NECESSARY TO PREVENT EXCESSIVE ACCUMULATION OF LINT.
07/06/2009 INSP - FULL Violation 2.)TFC 906.2 THE PORTABLE FIRE EXTINGUISHERS ARE PAST DUE FOR ANNUAL INSPECTION.
07/06/2009 INSP - FULL Violation 3.) TFC 703.1.1 REPLACE MISSING CEILING SHEETROCK IN EAST MECHANICAL ROOM ON 1ST FLOOR.
07/06/2009 INSP - FULL Violation 4.) TFC 703.1.1 SEAL OPEN PIPES IN WEST MECHANICAL ROOM 1ST FLOOR.
07/06/2009 INSP - FULL Violation 5.) TFC 605.4 REPLACE MULTI-PLUG ADAPTER IN GENERAL MANAGER'S OFFICE WITH A UL/FM LISTED POWER STRIP.
07/06/2009 INSP - FULL Violation 6.) TFC 605.6 A COVER PLATE IS REQUIRED ON FLOOR OUTLET IN PIANO ROOM.
07/06/2009 INSP - FULL Violation 7.) TFC 605.6 THE KITCHEN OUTLET FOR THE COFFEE MACHINE IS REQUIRED TO HAVE A COVER PLATE.
07/06/2009 INSP - FULL Violation 8.) TFC 904.5.1 THE KITCHEN HOOD EXTINGUISHING SYSTEM IS PAST DUE FOR 6 MO. INSPECTION.
07/06/2009 INSP - FULL Violation 9.) TFC 703.1.1 SEAL AROUND INCOMING TV CABLE IN PHONE ROOM.
07/06/2009 INSP - FULL Violation 10.) TFC 605.4 REPLACE MULTI-PLUG ADAPTER IN CHART ROOM WITH A UL/FM LISTED POWER STRIP.
07/06/2009 INSP - FULL Violation 11.) TFC 1011.1 REPLACE MISSING EXIT SIGN AT EAST END OF SOUTH HALLWAY.
07/06/2009 INSP - FULL Violation 12.) TFC 1011.4 INTERNALLY ILLUMINATED EXIT SIGN ABOVE 2ND FLOOR SOUTHEAST EXIT DOOR IS NOT ILLUMINATED.
07/06/2009 INSP - FULL Violation 13.) TFC 1011.4 INTERNALLY ILLUMINATED EXIT SIGN IN 2ND FLOOR HALLWAY OUTSIDE OF ACTIVITY ROOM IS NOT ILLUMINATED.
07/06/2009 INSP - FULL Violation 14.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN 2ND FLOOR LIBRARY.
07/06/2009 INSP - FULL Violation 15.) TFC 901.6.2 THE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM ARE PAST DUE FOR ANNUAL INSPECTION.