Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/10/2009 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
1.) TFC 316.2 LINT TRAP FOR CLOTHES DRYER MUST BE CLEANED OFTEN AS NECESSARY TO PREVENT EXCESSIVE ACCUMULATION OF LINT. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
2.)TFC 906.2 THE PORTABLE FIRE EXTINGUISHERS ARE PAST DUE FOR ANNUAL INSPECTION. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
3.) TFC 703.1.1 REPLACE MISSING CEILING SHEETROCK IN EAST MECHANICAL ROOM ON 1ST FLOOR. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
4.) TFC 703.1.1 SEAL OPEN PIPES IN WEST MECHANICAL ROOM 1ST FLOOR. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
5.) TFC 605.4 REPLACE MULTI-PLUG ADAPTER IN GENERAL MANAGER'S OFFICE WITH A UL/FM LISTED POWER STRIP. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
6.) TFC 605.6 A COVER PLATE IS REQUIRED ON FLOOR OUTLET IN PIANO ROOM. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
7.) TFC 605.6 THE KITCHEN OUTLET FOR THE COFFEE MACHINE IS REQUIRED TO HAVE A COVER PLATE. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
8.) TFC 904.5.1 THE KITCHEN HOOD EXTINGUISHING SYSTEM IS PAST DUE FOR 6 MO. INSPECTION. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
9.) TFC 703.1.1 SEAL AROUND INCOMING TV CABLE IN PHONE ROOM. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
10.) TFC 605.4 REPLACE MULTI-PLUG ADAPTER IN CHART ROOM WITH A UL/FM LISTED POWER STRIP. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
11.) TFC 1011.1 REPLACE MISSING EXIT SIGN AT EAST END OF SOUTH HALLWAY. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
12.) TFC 1011.4 INTERNALLY ILLUMINATED EXIT SIGN ABOVE 2ND FLOOR SOUTHEAST EXIT DOOR IS NOT ILLUMINATED. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
13.) TFC 1011.4 INTERNALLY ILLUMINATED EXIT SIGN IN 2ND FLOOR HALLWAY OUTSIDE OF ACTIVITY ROOM IS NOT ILLUMINATED. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
14.) TFC 703.1.1 REPLACE MISSING CEILING TILE IN 2ND FLOOR LIBRARY. |
| 07/06/2009 |
INSP - FULL |
|
Violation |
15.) TFC 901.6.2 THE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM ARE PAST DUE FOR ANNUAL INSPECTION. |