Case: T09FR02150

Parcel: 124161300


Addresses:

830 E 22ND ST

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/02/2009 INSP - FULL Violation 703.1 Maintenance. The required fire-resistance rating of
fire-resistance-rated construction (including walls, firestops,
shaft enclosures, partitions, smoke barriers, floors, fire-resistive
coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems) shall be
maintained. Such elements shall be properly repaired, restored
or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit,
wires, ducts, air transfer openings and holes made for any
reason shall be protected with approved methods capable of
resisting the passage of smoke and fire. Openings through
fire-resistance-rated assemblies shall be protected by self- or
automatic-closing doors of approved construction meeting the
fire protection requirements for the assembly.
703.1.1 Fireblocking and draftstopping. Required
fireblocking and draftstopping in combustible concealed
spaces shall be maintained to provide continuity and integrity
of the construction.
703.1.2 Smoke barriers. Required smoke barriers shall be
maintained to prevent the passage of smoke and all openings
protected with approved smoke barrier doors or smoke
dampers.
Fix all holes between offices and sales room.
07/02/2009 INSP - FULL Violation 605.4 Multiplug adapters. Multiplug adapters, such as cube
adapters, unfused plug strips or any other device not complying
with the ICC Electrical Code shall be prohibited.
605.4.1 Power tap design. Relocatable power taps shall be
of the polarized or grounded type, equipped with
overcurrent protection, and shall be listed in accordance
with UL 1363.
605.4.2 Power supply. Relocatable power taps shall be
directly connected to a permanently installed receptacle.
605.4.3 Installation. Relocatable power tap cords shall not
extend through walls, ceilings, floors, under doors or floor
coverings, or be subject to environmental or physical damage.
Do not piggyback strip plugs.
07/02/2009 INSP - FULL Violation 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
605.5.1 Power supply. Extension cords shall be plugged
directly into an approved receptacle, power tap or multiplug
adapter and, except for approved multiplug extension cords,
shall serve only one portable appliance.
Do not use extension cords for perminant wiring.
07/02/2009 INSP - FULL Violation 315.2.3 Equipment rooms. Combustible material shall not
be stored in boiler rooms, mechanical rooms or electrical
equipment rooms.315.2 Storage in buildings. Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
heaters or heating devices by distance or shielding so that ignition
cannot occur.
315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm)
below sprinkler head deflectors in sprinklered areas of
buildings.
Do not store combustible materials in Hot waterheater room.