Case: T09FR02148

Parcel: 11105026D

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/30/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
07/01/2009 INSP - FULL Violation 1.) TFC 1008.1.8.3 SIGN IS REQUIRED ABOVE FRONT EXIT DOOR STATING "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED".
07/01/2009 INSP - FULL Violation 2.) TFC 906.2 ALL PORTABLE FIRE EXTINGUISHERS ON PREMISES ARE DUE FOR ANNUAL INSPECTION.
07/01/2009 INSP - FULL Violation 3.) TFC 1008.1.8 THE DOUBLE KEYED DEAD BOLT ON REAR EXIT DOOR MUST BE REPLACED WITH A THUMB TURN LATCH.
07/01/2009 INSP - FULL Violation 4.) TFC 1011.1 AN EXIT SIGN IS REQUIRED ABOVE REAR EXIT DOOR TO SOUTH PARKING LOT.
07/01/2009 INSP - FULL Violation 5.) TFC 1011.1 AN EXIT SIGN IS REQUIRED AT EAST END OF SOUTH HALLWAY DOWNSTAIRS INDICATING DIRECTION TO SOUTH EXIT DOOR.
07/01/2009 INSP - FULL Violation 6.) TFC 1011.1 AN EXIT SIGN IS REQUIRED AT EACH END OF NORTH HALLWAY.
07/01/2009 INSP - FULL Violation 7.) TFC 1008.1.8 THE DOUBLE KEYED DEAD BOLT ON UPSTAIRS NORTH EXIT DOOR MUST BE REPLACED WITH A THUMB TURN LATCH ON INSIDE OF DOOR.
07/01/2009 INSP - FULL Violation 8.) TFC 1006.3 THE EMERGENCY ILUMINATION UNIT AT NORTH END OF UPSTAIRS HALLWAY NOT LIGHTING.
07/01/2009 INSP - FULL Violation 9.) TFC 901.6 THE MISSING SPRINKLER HEAD ESCUTCHEON IN UPSTAIRS HALLWAY, NORTH END, MUST BE REPLACED.
07/01/2009 INSP - FULL Violation 10.) TFC 901.6.2 THE SPRINKLER SYSTEM IS PAST DUE FOR ANNUAL INSPECTION.
07/01/2009 INSP - FULL Violation 11.) TFC 508.5.4 VEGETATION OBSTRUCTING ACCESS TO FDC.