Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR02065
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 6/26/09, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 100 / 150 N. TUCSON BLVD. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
06/26/2009 | INSP - FULL | Correction Required | DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR INVOICE TO BE FORWARDED TO THE FIRE PREVENTION OFFICE 1) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE 2) PRESSURE GUAGES ARE DUE FOR REPLACEMENT OR RECALIBRATON 3) THE HYDRAULIC CALCULATION PLATE AT THE SPRINKLER RISER, SHALL BE FILLED OUT, ENGRAVED, WITH SYSTEM CRITERIA |