Case: T09FR02065

Parcel: 12509005A


Addresses:

100 N TUCSON BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR02065

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/26/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 6/26/09, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 100 / 150 N. TUCSON BLVD. IF CORRECTED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
06/26/2009 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE REPAIR INVOICE TO BE FORWARDED TO THE FIRE PREVENTION OFFICE

1) THE 5 YEAR INTERNAL VALVE INSPECTION IS DUE

2) PRESSURE GUAGES ARE DUE FOR REPLACEMENT OR RECALIBRATON

3) THE HYDRAULIC CALCULATION PLATE AT THE SPRINKLER RISER, SHALL BE FILLED OUT, ENGRAVED, WITH SYSTEM CRITERIA