Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T09FR02062
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2009 | INSP - FULL | Violation | The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). 1.__Problem: There is no permit on file for your canopy. TFC 2403.4 Permits. Permits shall be required as set forth in Sections 105.6 and 105.7. You will apply for a permit from the City of Tucson Development Services Department. The permit will be posted on the wall of the patio for the fire inspector to approve. 2.__Problem: There is a missing escussion plate in your closet on the NorthWest corner of your restaurant. TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. You will have the escussion plate put in place by a trained professional. 3__. Problem:There is a gap between the fire resistive ceiling and the escussion plate for the sprinkler head. TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. You will have the escussion plate put in place by a trained professional. 5.__Problem: There is a keylocking cylinder on your inner security door that exits from the kitchen. 1008.1.8.3 Locks and latches. Key locking cylinder is not permitted to be used on main exits from the building only. You will replace the cylinder with a thumb bolt latch. The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated. Property Representative Signature: _________________________. Fire Inspector Signature: _________________________(791-4502). Reinspection Date: ___/___/___ or later. ___Approved ___Not Approved |