Case: T09FR02022

Parcel: 10509550A


Addresses:

4861 N STONE AV


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR02022

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/26/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 6/23/09, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 4861 N. STONE. IF COMPLETED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
06/23/2009 INSP - FULL Correction Required DURING THE LAST FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. PLEASE FORWARD A COPY OF THR REPAIR ORDER TO THE FIRE PREVENTION OFFICE.

1) THE GUAGES AT THE RISER ARE OVER FIVE YEARS OLD, AND DO NOT OPERATE CORRECTLY. THEY SHALL BE REPLACED OR RECALIBRATED.

2) THE RISER CHECK VALVE IS DUE FFOR A FIVE YEAR INTERNAL INSPECTION

3) SECURE THR SPRINKLER RISER CONTROL VALVE WITH A LOCK AND CHAIN

4) PROVIDE SIGNAGE FOR THE MAIN CONTROL VALVE