Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR02022
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 6/23/09, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 4861 N. STONE. IF COMPLETED HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
06/23/2009 | INSP - FULL | Correction Required | DURING THE LAST FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. PLEASE FORWARD A COPY OF THR REPAIR ORDER TO THE FIRE PREVENTION OFFICE. 1) THE GUAGES AT THE RISER ARE OVER FIVE YEARS OLD, AND DO NOT OPERATE CORRECTLY. THEY SHALL BE REPLACED OR RECALIBRATED. 2) THE RISER CHECK VALVE IS DUE FFOR A FIVE YEAR INTERNAL INSPECTION 3) SECURE THR SPRINKLER RISER CONTROL VALVE WITH A LOCK AND CHAIN 4) PROVIDE SIGNAGE FOR THE MAIN CONTROL VALVE |