Case: T09FR02006

Parcel: 13704135F


Addresses:

5505 S NOGALES HY


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR02006

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
06/22/2009 VIOL - MEANS OF EGRESS Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate…
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.

_____ Repair or replace batteries in emergency lighting
06/22/2009 VIOL - MEANS OF EGRESS Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.

_____ Repair/replace exit signs
06/22/2009 VIOL - MEANS OF EGRESS Violation 1014.4.1 - Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches.
Exception: Nonpublic aisles serving less than 50 people and not required to be accessible by Chapter 11 of the International Building Code need not exceed 28 inches in width.