Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T09FR02006

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
06/22/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers.
__Extend sprinkler coverage into Building B office.
06/22/2009 VIOL - FIRE PROTECTION SYSTEMS Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
___Server room building C.
06/22/2009 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request.