Case: T09FR01932

Parcel: 121064070


Addresses:

5751 E SPEEDWAY BL


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR01932

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
06/11/2009 VIOL - BUILDING SVCS & SYSTEMS Violation IFC.605.4 Multiplug adapters.
Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

____Remove/replace multi-plug adapter in storage room.

IFC.05.4.2 Power supply.
Relocatable power taps shall be directly connected to a permanently installed receptacle.

____Relocatable power strip by water cooler needs to be UL1363 approved.
06/11/2009 VIOL - BUILDING SVCS & SYSTEMS Violation IFC.605.5 Extension cords.
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

____Extension cord being used as permanent wireing by front desk.
____Extension cord being used as permanent wireing by refrigerator.