Case: T09FR01906

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T09FR01906

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2009 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
06/09/2009 INSP - FULL Violation 1.) TFC 703.1.1 SEAL HOLE IN CEILING TILE IN TECH MGMNT. FILE ROOM NEXT TO SUPV'S OFFICE.
06/09/2009 INSP - FULL Violation 2.) TFC 703.1.1 SEAL HOLE IN WALL FROM OLD FIRE EXTINGUISHER MOUNTING BRACKET OUTSIDE OF TECH MGMNT KITCHEN.
06/09/2009 INSP - FULL Violation 3.) TFC 703.1.1 TECH. CO-ORDINATOR'S OFFICE OF INPATIENT PHARMACY THERE ARE 4 HOLES IN CEILING TILES NEEDING TO BE SEALED.
06/09/2009 INSP - FULL Violation 4.) TFC 703.1.1 TECH. CO-ORDINATOR'S OFFICE OF INPATIENT PHARMACY THER ARE 4 SMALL HOLES BY DOOR.
06/09/2009 INSP - FULL Violation 5.) TFC 901.6 INPATIENT PHARMACY ADMIN. OFFICE HALLWAY OUTSIDE OF AL PATTERSON'S OFFICE THE MISSING SPRINKLER HEAD ESCUTCHEON MUST BE REPLACED.
06/09/2009 INSP - FULL Violation 6.) TFC 901.6 A SPRINKLER HEAD ESCUTCHEON IS MISSING IN AL PATTERSON'S OFFICE.
06/09/2009 INSP - FULL Violation 7.) TFC 605.6 INPATIENT PHARMACY DRUG INFORMATION AREA 2 ELECTRICAL OUTLETS UNDER WALL SHELF NEED A COVER PLATE INSTALLED.
06/09/2009 INSP - FULL Violation 8.) TFC 703.1.1 IN CENTRAL MONITORING AREA PBX PHONE ROOM ELECTRICAL CONDUIT AND COMM. CABLES MUST BE SEALED WHERE THEY PENERTATE THE CEILING.
06/09/2009 INSP - FULL Violation 9.) TFC 703.1.1 IN PBX PHONE ROOM THE WALL PENETRATION NEAR THE FLOOR, BY THE DOOR, MUST BE SEALED.
06/09/2009 INSP - FULL Violation 10.) TFC 901.6 THE MISSING SPRINKLER HEAD ESCUTCHEON IN HALLWAY OUTSIDE OF CENTRAL MONITORING MUST BE REPLACED.
06/09/2009 INSP - FULL Violation 11.) TFC 703.1.1 IN SECURITY DISPATCH THE WALL PENETRATION BY DOOR IN THE SOUTHEAST CORNER MUST BE SEALED.
06/09/2009 INSP - FULL Violation 12.) TFC 703.1.1 THE SQUARE CEILING PENETRATION ABOVE THE PBX OFFICE CUBICLE MUST BE SEALED.
06/09/2009 INSP - FULL Violation 13.) TFC 703.1.1 IN EMPLOYEE HEALTH THE HOLE IN THE CEILING TILE IN HALLWAY BY ENTRANCE DOOR MUST BE SEALED.