Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/24/2009 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
1.) TFC 703.1.1 SEAL HOLE IN CEILING TILE IN TECH MGMNT. FILE ROOM NEXT TO SUPV'S OFFICE. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
2.) TFC 703.1.1 SEAL HOLE IN WALL FROM OLD FIRE EXTINGUISHER MOUNTING BRACKET OUTSIDE OF TECH MGMNT KITCHEN. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
3.) TFC 703.1.1 TECH. CO-ORDINATOR'S OFFICE OF INPATIENT PHARMACY THERE ARE 4 HOLES IN CEILING TILES NEEDING TO BE SEALED. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
4.) TFC 703.1.1 TECH. CO-ORDINATOR'S OFFICE OF INPATIENT PHARMACY THER ARE 4 SMALL HOLES BY DOOR. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
5.) TFC 901.6 INPATIENT PHARMACY ADMIN. OFFICE HALLWAY OUTSIDE OF AL PATTERSON'S OFFICE THE MISSING SPRINKLER HEAD ESCUTCHEON MUST BE REPLACED. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
6.) TFC 901.6 A SPRINKLER HEAD ESCUTCHEON IS MISSING IN AL PATTERSON'S OFFICE. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
7.) TFC 605.6 INPATIENT PHARMACY DRUG INFORMATION AREA 2 ELECTRICAL OUTLETS UNDER WALL SHELF NEED A COVER PLATE INSTALLED. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
8.) TFC 703.1.1 IN CENTRAL MONITORING AREA PBX PHONE ROOM ELECTRICAL CONDUIT AND COMM. CABLES MUST BE SEALED WHERE THEY PENERTATE THE CEILING. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
9.) TFC 703.1.1 IN PBX PHONE ROOM THE WALL PENETRATION NEAR THE FLOOR, BY THE DOOR, MUST BE SEALED. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
10.) TFC 901.6 THE MISSING SPRINKLER HEAD ESCUTCHEON IN HALLWAY OUTSIDE OF CENTRAL MONITORING MUST BE REPLACED. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
11.) TFC 703.1.1 IN SECURITY DISPATCH THE WALL PENETRATION BY DOOR IN THE SOUTHEAST CORNER MUST BE SEALED. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
12.) TFC 703.1.1 THE SQUARE CEILING PENETRATION ABOVE THE PBX OFFICE CUBICLE MUST BE SEALED. |
| 06/09/2009 |
INSP - FULL |
|
Violation |
13.) TFC 703.1.1 IN EMPLOYEE HEALTH THE HOLE IN THE CEILING TILE IN HALLWAY BY ENTRANCE DOOR MUST BE SEALED. |