Case: T09FR01904

Parcel: 117040720


Addresses:

621 N 4TH AV


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR01904

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/09/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring. Extension cords
and flexible cords shall not be affixed to structures, extended
through walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.

_____1. Remove the extension cord used to power the OPEN sign.
NOTE: Replace it with a fused power-strip.
06/09/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes.

_____1. Replace the missing electrical cover located in the electrical closet.